How do I test a PNOZ, for example, in accordance with BetrSichV? Is it sufficient to trigger the emergency stop function via an emergency stop switch and to test the switch-off action of the PNOZ?

The industrial safety regulations (BetrSichV) stipulate that the whole safety function must be tested. This means from the sensor to the actuator. The functions monitored via the PNOZ do not need to be retested separately.

The industrial safety regulations also require the test to be carried out by a competent person.

Competent person:

http://www.wissen-maschinensicherheit.de/faq/content/9/11/de/was-ist-eine-befaehigte-person.html

Headoffice

Pilz GmbH & Co. KG
Felix-Wankel-Straße 2
73760 Ostfildern
Germany

Telephone: +49 711 3409-0
E-Mail: pilz.gmbh@pilz.de

Technical Support

Telephone: +49 711 3409 444
E-Mail: support@pilz.com

Americas

  • Mexico: +52 55 5572 1300
  • Canada: +1 888-315-PILZ (315-7459)
  • United States (toll-free): +1 877-PILZUSA (745-9872)
  • Brazil: + 55 11 4942-7028

Europe

  • Turkey: +90 216 5775552
  • Italy: +39 0362 1826711
  • Russia: +74956654993
  • Spain: +34 938497433
  • Sweden: +46 300 13990 / +45 74436332
  • Germany: +49 711 3409 444
  • Belgium: +32 9 321 75 75
  • Netherlands: +31 347 320477
  • Finland: +358 10 3224030 / +45 74436332
  • France (toll-free): +33 3 88104000
  • Switzerland: +41 62 88979 30
  • Ireland: +353 21 4804983
  • Austria: +43 1 7986263-444
  • Denmark: +45 74436332
  • United Kingdom: +44 1536 462203

Asia Pacific

  • New Zealand: +64 9 6345350
  • South Korea: +82 31 778 3390
  • China: +86 21 60880878-216
  • Taiwan: +886 2 25681600
  • Japan: +81 45 471 2281
  • Australia: +61 3 9560 0621