How do I test a PNOZ, for example, in accordance with BetrSichV? Is it sufficient to trigger the emergency stop function via an emergency stop switch and to test the switch-off action of the PNOZ?

The industrial safety regulations (BetrSichV) stipulate that the whole safety function must be tested. This means from the sensor to the actuator. The functions monitored via the PNOZ do not need to be retested separately.

The industrial safety regulations also require the test to be carried out by a competent person.

Competent person:

http://www.wissen-maschinensicherheit.de/faq/content/9/11/de/was-ist-eine-befaehigte-person.html

Headoffice

Pilz GmbH & Co. KG
Felix-Wankel-Straße 2
73760 Ostfildern
Germany

Telephone: +49 711 3409-0
E-Mail: pilz.gmbh@pilz.de

Technical Support

Telephone: +49 711 3409 444
E-Mail: support@pilz.com

Americas

  • United States (toll-free): +1 877-PILZUSA (745-9872)
  • Canada: +1 888-315-PILZ (315-7459)
  • Mexico: +52 55 5572 1300
  • Brazil: + 55 11 4942-7028

Europe

  • Finland: +358 10 3224030 / +45 74436332
  • United Kingdom: +44 1536 462203
  • Austria: +43 1 7986263-444
  • Denmark: +45 74436332
  • Turkey: +90 216 5775552
  • Sweden: +46 300 13990 / +45 74436332
  • Ireland: +353 21 4804983
  • France (toll-free): +33 3 88104000
  • Netherlands: +31 347 320477
  • Germany: +49 711 3409 444
  • Switzerland: +41 62 88979 32
  • Russia: +7 495 6654993
  • Spain: +34 938497433
  • Italy: +39 0362 1826711
  • Belgium: +32 9 321 75 70

Asia Pacific

  • Taiwan: +886 2 25700068
  • China: +86 400-088-3566
  • South Korea: +82 31 778 3390
  • New Zealand: +64 9 6345350
  • Japan: +81 45 471 2281
  • Australia: +61 3 9560 0621