{"id":"760100","name":"PMD s10 24-240VACDC","price":"0.00","currency":"TWD","category":null}
Actual product may vary
PMD s10 24-240VACDC
Product ID: 760100
True power monitoring device for measuring and monitoring the
true power of electrical loads,
limit values that can be set via display, can be saved to chip card,relay output: 2
changeover contacts, a...
More
Please note that the housing colour has changed temporarily. This does not adversely affect functionality.
Further information is available at Sales Information – 229402 .
This product is no longer available. For more information on successor products or replacement parts, please contact Technical Support.
On request
Available soon
Available ex-stock
On request
True power monitoring device for measuring and monitoring the
true power of electrical loads,
limit values that can be set via display, can be saved to chip card,relay output: 2
changeover contacts, analogue output: 4 - 20 mA and 0 - 10 V DC
operating voltage: 24 - 240 V AC/DC, measuring voltage: 100 - 550 V AC,
measuring current: 1 - 12 A, screw terminals.
Technical data
Electrical data
Supply voltage (V) |
24 - 240
V |
Type of supply voltage U1 |
AC/DC
|
Power consumption AC |
5
VA |
Power consumption DC |
3
W |
Max. device circuit breaker |
Max. conductor cross section
|
Measuring circuit
U meas. range analogue input |
100 - 550
V |
I meas. range analogue input |
1 - 12
A |
Freq. meas. range analog i/p |
0, 15 - 400 Hz
|
Output signals during motor operation
Uout during motor mode 10-0 V |
10 - 0 V
|
Output signals during generator operation
Uout during generator mode |
0 - -10 V
|
Iout during generator mode |
0 - -20 mA
|
Relay outputs
Utilisation cat. AC/DC1 stand. |
EN 60947-4-1
|
Utilisation cat. AC15/DC13sta. |
EN 60947-5-1
|
Safety contacts: AC at UL |
240 VAC G. U.
|
Relay contact material |
AgNi10
|
Environmental data
Climatic suitability to ... |
EN 60068-2-78
|
Ambient temperature |
-10 - 55
°C |
Condensation permitted? |
Not permitted
|
EMC to standard ... |
EN 61000-6-2
EN 61000-6-4
|
Vibration to standard ... |
EN 60068-2-6
|
Clearance & creepage dist. to |
EN 60664-1
|
Overvoltage category |
III / II
|
Pollution degree clear.&creep. |
2
|
Protection type, mounting |
|
Protection type, housing |
|
Terminal protection type |
|
Times
React.time analog o/p 15-60 Hz |
70 - 16 ms
|
Mechanical data
Mounting position |
any
|
Housing material lower section |
PC
|
Housing material front plate |
PC
|
Housing material upper part |
PC
|
Connection terminal |
Screw terminal
|
Terminal style |
plug-in
|
Flex. cond. c/s AWG info |
24 - 12 AWG
|
Height dimension |
98
mm |
Width dimension |
45
mm |
Depth dimension |
120
mm |
Net weight |
340
g |
Gross weight |
350
g |
Environment
REACh compliance |
contains min. 1 SVHC-substance
|
WEEE classifikation (08/2018) |
5 devices (feed size < 50cm)
|
Commercial data
Harmonized System Code |
90303370
|
EAN-Code |
4046548051865
|
ECLASS version |
ECLASS-13
|
ECLASS Reference Feature |
27371806
|
ETIM Version |
ETIM-9.0
|
ETIM Reference Group |
EG000019
|
ETIM Reference Feature |