Ireland | english

Sensor technology

Non-contact magnetic safety switches PSENmag

What is the maximum Performance Level I can achieve with PSENmag?

  • PL e is possible with a single connection.
  • With a series connection this drops to PL d or PL c due to faults potentially being concealed, see ISO 24119.